Three-Phase AC Power & Power Factor (IEEE 141)

FORMULA SOLVERIEEE 141 (Electric Power Distribution)IEC 60038 (Standard voltages)

Calculate balanced three-phase AC real power (kW), apparent power (kVA), reactive power (kVAR), line current, and power factor correction.

Loading...
▸Formula · assumptions · example(IEEE 141 (Electric Power Distribution) · IEC 60038 (Standard voltages) · NFPA 70 (NEC Article 220))

Formula

P=3⋅VL⋅IL⋅cos⁡ϕ1000[kW],S=3⋅VL⋅IL1000[kVA],Q=3⋅VL⋅IL⋅sin⁡ϕ1000[kVAR]P = \frac{\sqrt{3} \cdot V_L \cdot I_L \cdot \cos\phi}{1000} \quad [\text{kW}], \quad S = \frac{\sqrt{3} \cdot V_L \cdot I_L}{1000} \quad [\text{kVA}], \quad Q = \frac{\sqrt{3} \cdot V_L \cdot I_L \cdot \sin\phi}{1000} \quad [\text{kVAR}]

Balanced three-phase AC electric power per IEEE 141 and IEC 60038. Explicitly defines unit scaling: when line voltage VL is in Volts and line current IL in Amperes, dividing by 1000 converts primary Volt-Amperes (VA) and Watts (W) to kVA and kW.

Assumptions

  • · Symmetrical balanced three-phase AC system with 120° electrical phase displacement between phase conductors
  • · Line-to-line voltage VL and line current IL specified as RMS values
  • · Active, reactive, and apparent power related by the power triangle identity: S² = P² + Q²
REFERENCE WORKED EXAMPLE · TEXTBOOK BASELINE (NOT LIVE INPUT)
IEEE 141 / IEC 60038

Three-Phase Balanced Motor Load Power & Energy Analysis (400V / 25A)

BASELINE STATUS: PASS(W/kW and VA/kVA scaling verified; power triangle closure S = √(P²+Q²) confirmed)

Determination of active, reactive, and apparent power with explicit W/kW and VA/kVA unit conversion factors.

1. Inputs & Boundary Parameters
Line-to-line RMS voltage VL400.0 V
Line RMS current IL25.0 A
Load power factor cos φ0.85 [-]
2. Applied Governing Equations & Standards
Apparent Power:
S=(√3⋅VL⋅IL)/1000S = (√3 · VL · IL) / 1000
IEEE 141
Active Real Power:
P=S⋅cosφ=(√3⋅VL⋅IL⋅cosφ)/1000P = S · cos φ = (√3 · VL · IL · cos φ) / 1000
Real Work Power
Reactive Power:
Q=S⋅sinφ=S⋅√(1−cos2φ)Q = S · sin φ = S · √(1 - cos² φ)
Magnetizing Reactive
Power Triangle Check:
S=√(P2+Q2)S = √(P² + Q²)
Complex Power Proof
3. Intermediate Calculation Stages
Displacement factor sin φ0.5268
Unscaled apparent power17,321
Unscaled active power14,722
Unscaled reactive power9,125
4. Reference Benchmark Verification & Acceptance ThresholdBENCHMARK: PASS
Active, Reactive & Apparent Power: P = 14.72 kW | S = 17.32 kVA | Q = 9.12 kVAR
Acceptance limit: cos φ = 0.85 (Industrial compliance threshold ≥ 0.85)