HVAC Heating & Cooling Thermal Load

FORMULA SOLVERASHRAE Fundamentals HandbookISO 52000 (Energy performance of buildings)

Deterministic engineering intelligence platform for mechanical, structural, and electrical designers. Standard-referenced calculation engines, 3D CAD workspace, and transparent engineering equations.

Loading...
▸Formula · assumptions · example(ASHRAE Fundamentals Handbook · ISO 52000 (Energy performance of buildings) · EN 12831)

Formula

Q˙sensible=1.23⋅V˙⋅ΔT,Q˙total=U⋅A⋅ΔTcltd+Q˙solar+Q˙internal\dot{Q}_{\text{sensible}} = 1.23 \cdot \dot{V} \cdot \Delta T, \quad \dot{Q}_{\text{total}} = U \cdot A \cdot \Delta T_{\text{cltd}} + \dot{Q}_{\text{solar}} + \dot{Q}_{\text{internal}}

ASHRAE cooling and heating load calculation, building envelope overall U-factor, solar heat gain coefficient (SHGC), and sensible/latent heat breakdown.

Assumptions

  • · Steady-state heat transfer through building envelope layers (insulation, brick, glazing)
  • · Cooling Load Temperature Difference (CLTD) accounts for thermal mass time lag
  • · Internal heat gains include occupant sensible/latent metabolic rate and equipment wattage
REFERENCE BASELINE EXAMPLE

Worked example — Production Office Space (Area = 120 m², ΔT = 15 K, Occupants = 10, Equipment = 3 kW)

Envelope transmission = 4.2 kW, Ventilation sensible = 2.2 kW, Internal load = 4.3 kW -> Total design cooling load = 10.7 kW (3.05 Tons Refrigeration).