Cable Sizing & Voltage Drop (IEC 60287)

FORMULA SOLVERIEC 60364-5-52:2009NFPA 70 / NEC 210.19(A) & 215.2(A)

Deterministic engineering intelligence platform for mechanical, structural, and electrical designers. Standard-referenced calculation engines, 3D CAD workspace, and transparent engineering equations.

Loading...
▸Formula · assumptions · example(IEC 60364-5-52:2009 · NFPA 70 / NEC 210.19(A) & 215.2(A) · DIN VDE 0100-520)

Formula

ρ(T)=ρ20[1+α(T−20∘C)],ΔV=2⋅L⋅I⋅ρ(T)⋅cos⁡ϕA(Single-phase),ΔV=3⋅L⋅I⋅ρ(T)⋅cos⁡ϕA(Three-phase)\rho(T) = \rho_{20} [1 + \alpha(T - 20^\circ\text{C})], \quad \Delta V = \frac{2 \cdot L \cdot I \cdot \rho(T) \cdot \cos\phi}{A} \quad (\text{Single-phase}), \quad \Delta V = \frac{\sqrt{3} \cdot L \cdot I \cdot \rho(T) \cdot \cos\phi}{A} \quad (\text{Three-phase})

Conductor line impedance and voltage drop analysis per IEC 60364-5-52 and NEC Article 210/215. Incorporates temperature coefficient α = 0.00393 / °C for copper. Note: 20°C gives reference baseline (2.48%); operating temperature (e.g. 70°C under continuous full load) elevates resistivity to ρ70 ≈ 0.02130 Ω·mm²/m and drop to 2.96%, approaching the 3.00% branch circuit threshold.

Assumptions

  • · Standard reference temperature 20°C: ρ20 = 0.0178 Ω·mm²/m for commercial copper (or 0.01724 for annealed pure copper)
  • · Operating temperature correction applied via linear thermal model: ρ(T) = ρ20 · [1 + α · (T - 20°C)]
  • · For cross-sections A < 50 mm², inductive reactance XL is negligible; for A ≥ 50 mm² or low power factor, complex AC impedance Z = R·cos φ + XL·sin φ must be evaluated
  • · Maximum allowable voltage drop typically ≤ 3.0% for branch circuits, ≤ 5.0% for total feeder + branch circuit
REFERENCE WORKED EXAMPLE · TEXTBOOK BASELINE (NOT LIVE INPUT)
IEC 60364-5-52 / DIN VDE 0100-520

Single-Phase Branch Circuit Voltage Drop (230 V / 16 A, 20°C vs 70°C)

BASELINE STATUS: PASS(+0.52% margin at 20°C, tightens to +0.04% margin at 70°C operating temp)

Verification of terminal voltage drop across a 25-meter 2.5 mm² copper cable delivering 16 A at 230 V, contrasting 20°C reference and 70°C operating conditions.

1. Inputs & Boundary Parameters
System voltage V_nom230.0 V
Line current I16.00 A
One-way cable length L25.0 m
Conductor cross-section A2.50 mm²
Copper resistivity ρ20 (@ 20°C)0.0178 Ω·mm²/m
Conductor operating temperature Top70.0 °C
Temperature coefficient α0.00393 1/°C
2. Applied Governing Equations & Standards
Temperature-Corrected Resistivity:
ρ(T)=ρ20⋅[1+α⋅(Top−20)]ρ(T) = ρ20 · [1 + α · (Top - 20)]
IEC 60228
Reference Voltage Drop (20°C):
ΔV20=(2⋅L⋅I⋅ρ20)/AΔV20 = (2 · L · I · ρ20) / A
IEC 60364-5-52
Operating Voltage Drop (70°C):
ΔV70=(2⋅L⋅I⋅ρ70)/AΔV70 = (2 · L · I · ρ70) / A
IEC 60364-5-52
Percentage Drop:
%ΔV = (ΔV / V_nom) · 100
DIN VDE 0100-520
3. Intermediate Calculation Stages
Operating resistivity ρ700.02130
Loop resistance @ 20°C0.356
Loop resistance @ 70°C0.426
Terminal drop @ 20°C5.70
Terminal drop @ 70°C6.82
4. Reference Benchmark Verification & Acceptance ThresholdBENCHMARK: PASS
Percentage Voltage Drop %ΔV (20°C / 70°C): 2.48% (@ 20°C) | 2.96% (@ 70°C)
Acceptance limit: ≤ 3.00% (Branch Circuit Limit)